ND4 Non-indicating type
– Simple temperature set up
– Proportioning control or ON/OFF control
– Burn out (Output OFF when sensor disconnected)
– Plug in type(simple correcting, checking and exchanging)
· Suffix code
(Note) Specify the power supply voltage of ND4 separately. 110 V a.c. or 220 V a.c. |
· Specification
[ Input ] |
thermocouple | K |
Thermoresistor | Pt100 Ω(IEC751) |
Input impedance | Approx. 1 MΩ(Thermocouple input) |
Allowable signal source resistance | Max. 100 Ω (thermocouple input) |
Allowable wiring resistance | Resistance thermometer 10 Ω or less. (The resistance between the three lines should be the same) |
Allowable input voltage | Within ± 10 V (thermocouple, RTD, DC voltage) |
Reference contact compensation error | ±2.0 ℃ (0 ~ 50 ℃) |
[ Control functions and outputs ] |
[ General Specifications ] |
Power supply voltage | 110 V a.c. or 220 V a.c. individual |
Permissible Voltage Fluctuation Range | Rated Voltage ±10 % |
Consumption Power | Max. 3 VA |
Insulation Resistance | Min.20 MΩ (500 V d.c.) |
Dielectric Strength | 2000 V a.c. 50~60 Hz for 1 minute (Between different live parts) |
Ambient Temperature | 0 ~ 50 ℃ |
Ambient Humidity | 35 ~ 85 % R.H (without condensation) |
Storage temperature | -25 ~ 65 ℃ |
Shock Resistance | 300 m/s² |
Weight | 220g |
[ Standard Range ] |
Code | Input | Range (℃) |
1 | Pt | -50 ~ 50 |
2 | Pt | -100 ~ 100 |
3 | Pt | 0 ~ 100 |
5 | K, Pt | 0 ~ 200 |
6 | K, Pt | 0 ~ 300 |
7 | K, Pt | 0 ~ 400 |
Đánh giá