BX8-00
BX8-01
BX8-02
BX8-03
BX8-10
BX8-11
BX8-12
BX8-13
· Suffix code
Model | Suffix code | Description | |
BX8 | Board type digital temperature controller | ||
Control type | 0 | universal | |
1 | Heating / Cooling | ||
Selection | 0 | SV2, SV3 | |
1 | HBA | ||
2 | RS485 | ||
3 | RS485 / HBA |
· Specification
Model | BX8 | ||||||||||||||||
Function |
| ||||||||||||||||
Input Type |
| ||||||||||||||||
Sampling Cycle | 250 ms | ||||||||||||||||
Input Display Resolution | Basically, below the decimal point of the input signal and measuring range | ||||||||||||||||
Input Impedance | Thermocouple or mV input : above 1 MΩ, d.c V input : approx. 1 MΩ | ||||||||||||||||
Permissible resistance of signal source | Thermocouple : below 250 Ω, Voltage : below 2 kΩ | ||||||||||||||||
Permissible wiring resistance | RTD : below 150 Ω / single wire(but, the resistance of the 3 wires should be the same | ||||||||||||||||
Permissible input resistance | Within ±10V(Thermocouple, RTD, Voltage : mV d.c), Within ±20V(Voltage : V d.c) | ||||||||||||||||
Noise rejection ratio |
| ||||||||||||||||
Applied standard | Thermocouple / RTD(KS / IEC / DIN) | ||||||||||||||||
Compensation error at standard contact | ±1.5 °C(15 ~ 35 °C), ±2.0 °C(0 ~ 50 °C) | ||||||||||||||||
BURN-OUT detection |
| ||||||||||||||||
Measuring Accuracy | ±0.5%(FULL SCALE) | ||||||||||||||||
Input Range |
| ||||||||||||||||
Power of operating sensors | 20 V d.c(internal resistance 1.2 kΩ) Max. 50 mA, 15 V d.c (internal resistance 790 Ω) |
Đánh giá
Chưa có đánh giá nào.