ND4 Non-indicating type
– Simple temperature set up
– Proportioning control or ON/OFF control
– Burn out (Output OFF when sensor disconnected)
– Plug in type(simple correcting, checking and exchanging)
· Suffix code
| (Note) Specify the power supply voltage of ND4 separately. 110 V a.c. or 220 V a.c. | 
· Specification
| [ Input ] | 
| thermocouple | K | 
| Thermoresistor | Pt100 Ω(IEC751) | 
| Input impedance | Approx. 1 MΩ(Thermocouple input) | 
| Allowable signal source resistance | Max. 100 Ω (thermocouple input) | 
| Allowable wiring resistance | Resistance thermometer 10 Ω or less. (The resistance between the three lines should be the same) | 
| Allowable input voltage | Within ± 10 V (thermocouple, RTD, DC voltage) | 
| Reference contact compensation error | ±2.0 ℃ (0 ~ 50 ℃) | 
| [ Control functions and outputs ] | 
| [ General Specifications ] | 
| Power supply voltage | 110 V a.c. or 220 V a.c. individual | 
| Permissible Voltage Fluctuation Range | Rated Voltage ±10 % | 
| Consumption Power | Max. 3 VA | 
| Insulation Resistance | Min.20 MΩ (500 V d.c.) | 
| Dielectric Strength | 2000 V a.c. 50~60 Hz for 1 minute (Between different live parts) | 
| Ambient Temperature | 0 ~ 50 ℃ | 
| Ambient Humidity | 35 ~ 85 % R.H (without condensation) | 
| Storage temperature | -25 ~ 65 ℃ | 
| Shock Resistance | 300 m/s² | 
| Weight | 220g | 
| [ Standard Range ] | 
| Code | Input | Range (℃) | 
| 1 | Pt | -50 ~ 50 | 
| 2 | Pt | -100 ~ 100 | 
| 3 | Pt | 0 ~ 100 | 
| 5 | K, Pt | 0 ~ 200 | 
| 6 | K, Pt | 0 ~ 300 | 
| 7 | K, Pt | 0 ~ 400 | 



 
      


 
				 
				 
				 
				 
				 
				 
				 
				 
Reviews